FiltersUSA.com With discount code: GeoJohn receive a 10% discount.
Performance Troubleshooting | Htg | Clg | Possible Cause | Solution |
---|---|---|---|---|
Insufficient capacity | X | X | Dirty Filter | Replace or clean |
Not cooling or heating properly | X | Reduced or no Air flow in heating | Check for dirty air filter and clean or replace Check fan motor operation and airflow restrictions Too high of external static. Check static vs blower table | |
X | Reduced or no Air flow in cooling | Check for dirty air filter and clean or replace Check fan motor operation and airflow restrictions Too high of external static. Check static vs blower table | ||
X | X | Leaky duct work | Check supply and return air temperatures at the unit and at distant duct registers if significantly different, duct leaks are present | |
Unit Doesn't Operate in Cooling | X | X | Low refrigerant charge | Check superheat and subcooling per chart |
X | X | Restricted metering device | Check superheat and subcooling per chart. Replace. | |
X | Defective Reversing Valve | Perform RV touch test | ||
X | X | Thermostat improperly located | Check location and for air drafts behind stat | |
X | X | Unit undersized | Recheck loads & sizing check sensible clg load and heat pump capacity | |
X | X | Scaling in water heat exchanger | Perform Scaling check and clean if necessary | |
X | X | Inlet Water too Hot or Cold | Check load, loop sizing, loop backfill, ground moisture. | |
High Head Pressure | X | Reduced or no Air flow in heating | Check for dirty air filter and clean or replace Check fan motor operation and airflow restrictions Too high of external static. Check static vs blower table | |
X | Reduced or no water flow in cooling | Check pump operation or valve operation/setting Check water flow adjust to proper flow rate | ||
X | Inlet Water too Hot | Check load, loop sizing, loop backfill, ground moisture. | ||
X | Air Temperature out of range in heating | Bring return air temp within design parameters | ||
X | Scaling in water heat exchanger | Perform Scaling check and clean if necessary | ||
X | X | Unit Overcharged | Check superheat and subcooling. Reweigh in charge | |
X | X | Non-condensables in system | Vacuum system Reweigh in charge | |
X | X | Restricted metering device Low Suction Pressure | Check superheat and subcooling per chart. Replace. | |
Low suction pressure | X | Reduced water flow in heating | Check pump operation or water valve operation/setting Plugged strainer or filter. Clean or replace. Check water flow adjust to proper flow rate | |
X | Water Temperature out of range | Bring water temp within design parameters | ||
X | Reduced Air flow in cooling | Check for dirty air filter and clean or replace Check fan motor operation and airflow restrictions Too high of external static. Check static vs blower table | ||
X | Air Temperature out of range | Too much cold vent air? Bring entering air temp within design parameters | ||
X | X | Insufficient charge | Check for refrigerant leaks | |
Low discharge air temperature in heating |
X | Too high of air flow | Check fan motor speed selection and airflow chart | |
X | Poor Performance | See 'Insufficient Capacity' | ||
High humidity | X | Too high of air flow | Check fan motor speed selection and airflow chart |
|
X | Unit oversized | Recheck loads & sizing check sensible clg load and heat pump capacity |